UPS systems and generator services are operations that Computer Power Protection (CPP) specialises in.
Recommended UPS Maintenance
The Health & Safety Executive has issued a bulletin highlighting the importance of ongoing maintenance and servicing of your UPS system. As a supplier, it is CPP's responsibility to provide further details of the HSE bulletin.
The bulletin can be accessed at www.hse.gov.uk/safetybulletins/ups-systems-industrial-maintenance.htm
Computer Power Protection (Sales) are here to help and to carry out any UPS service requirement you may have.
Don't hesitate to get in touch with us at 01243 553167 or email info@cppsales.com.
10kVA UPS and above
Every 6 or 12 months:
- Visual Checks – Confirm the cleanliness of all fan grills and air inlets/outlets, and perform cleaning if needed. We ensure that all fans are in proper working condition. If feasible, visually examine all batteries and terminals for any signs of corrosion or swelling. Also, confirm that the environment surrounding the UPS meets the necessary criteria, including ambient temperature and the absence of corrosive or damp atmospheres.
- Performance Checks – Carry out a mains failure test to verify correct battery operation. This test can also be used to prove the UPS still meets the required autonomy. (Note: If the UPS still provides power to the critical load. This will be at risk during this test) Perform a transfer to and from Static bypass test to prove the correct bypass operation.
Every 3 to 4 years:
- Battery Change – for all units that are supplied with 5-year design life batteries as standard, to ensure maximum performance it is recommended to replace the batteries every 3 or 4 years.
Between 5 to 7 years:
- UPS Overhauls – Capacitors and fans are to be replaced. The model of UPS determines exactly when in the lifespan of the UPS these fans and capacitors are replaced however its typically between years 5 to 7. We recommend only carrying out 2 overhauls on a UPS before completely replacing it. (For our Modular UPS Multipower, replacement would on require a replacement Power Module)
Every 7 to 8 years:
- Battery Replacement – for all units that are supplied with 10-year design life batteries as standard, to ensure maximum performance it is recommended to replace the batteries every 7 to 8 years.
10kVA UPS and below
Every 6 or 12 months:
- Visual Checks – Confirm all fan grills and air inlets/outlets are clear from dust and debris. Clean where necessary. Confirm all fans are operating. If possible, visually inspect all batteries and terminals for signs of corrosion or swelling. Ensure the environment is suitable for the UPS (Ambient temperature and corrosive/damp atmosphere)
- Performance Checks – Carry out a mains failure test to verify correct battery operation. If required, this test can also be used to prove the UPS still meets the required autonomy. (Note: If the UPS is still providing power to the critical load. This will be at risk during this test)
Every 3 to 4 years:
- Battery Replacement – All units are supplied with 5-year design life batteries as standard. To ensure maximum performance it is recommended to replace the batteries every 3 or 4 years.
Every 10 years:
Full UPS Replacement – It is recommended that the UPS is replaced after 10 years of operation.
If you have any questions about UPS system of generator maintenance or servicing contact CPP and we will help you select the right service for your backup power.
CPP engineers are trained to work on many different UPS brands, so are experts in providing the right support for your system.