Riello UPS System Sentryum Rack 60kVA SRT 60 PWC power module for installation in Sentryum Rack Cabinet. Three phase input/Three phase output. Fitted with parallel card and dual input as standard.
Compatible with industrial environments
The basic building block is a 60 kVA/kW module.
Riello UPS System Sentryum Rack 60kVA SRT 60 PWC is a transformerless online 60kVA UPS designed specifically for critical industrial applications and other settings prone to harsh environmental conditions (i.e. dust, humidity, chemical particles)
High efficiency
Sentryum is a true ON LINE double conversion UPS system providing the very highest levels of power availability, flexibility and unrivalled energy efficiency with superior performance for any small Data Centre and mission critical applications.
Compactness
Modern guidelines and sustainable best
practices direct us to conceive and design
UPS with particular focus on the entire
product life cycle, therefore applying
ultimate but resilient technologies, recyclable materials and miniaturisation of assemblies whilst ensuring the systems global reliability, which is pivotal for any UPS
Riello UPS System Sentryum Rack 60kVA SRT 60 PWC features a unique control system that provides filtering and power factor correction upstream of the UPS, reducing harmonic distortion (<1% at resistive load and < 1.5% at non-linear load).
It has the capacity to handle high short circuits (i.e. 150% for 300 msec) and overloads (i.e. 150% for 1 minute), ensuring the UPS can deal with sudden peak loads without the need to transfer to bypass.
Riello UPS System Sentryum Rack 60kVA SRT 60 PWC comes with ‘Cold Start’ functionality that enables the UPS to start from battery power if there’s an issue with the mains supply.
• Extensive range of solutions
• Compactness
• Efficiency up to 96.5%
• High power availability
• Smart Battery Management
• Maximum reliability
• Flexibility of use
• Graphic touch screen display
MODELS | Single-phase output (SRM)
from 20 kVA/kW to 160 kVA/kW |
Three-phase output (SRT)
from 20 kVA/kW to 160 kVA/kW |
INPUT | ||
Rated voltage [V] | 220 / 230 / 240 single-phase + N and 380 / 400 / 415 three-phase + N | |
Rated frequency [Hz] | 50 / 60 | |
Voltage tolerance [V] | 230 / 400 ±20% @ full load1 | |
Frequency tolerance [Hz] | 40 - 72 | |
Power factor @ full load | 0.99 | |
Current distortion | THDI ≤3% | |
BYPASS | ||
Rated voltage [V] | 220 / 230 / 240 single-phase + N | 380 / 400 / 415 three-phase + N |
Number of phases | 1 + N | 3 + N |
Voltage tolerance (ph-N) [V] | from 180 (adjustable 180-200) to 264 (adjustable 250-264) referring to neutral | |
Rated frequency [Hz] | 50 or 60 (selectable) | |
Frequency tolerance | ±5% (selectable) | |
Bypass overload | 110% infinite, 125% for 60 min, 150% for 10 min | |
OUTPUT | ||
Nominal power [kVA] | 20 | |
Active power [kW] | 20 | |
Power factor | 1 up to 40 °C | |
Number of phases | 1 + N | 3 + N |
Rated voltage [V] | 2201 / 230 / 240 single-phase + N (selectable) | 3801 / 400 / 415 three-phase + N (selectable) |
Rated frequency [Hz] | 50 or 60 | |
Frequency stability on battery operation | 0.01% | |
Voltage stability | ±1% | |
Dynamic stability | EN 62040-3 class performance 1 non-linear load | |
Voltage distortion | <1% with resistive linear load / ≤1.5% with non-linear load | |
BATTERIES | ||
Type | VRLA AGM/GEL/NiCd/Li-ion/SuperCaps | |
Recharging method | One level, Two level, Cyclic recharge (selectable) | |
OVERALL SPECIFICATIONS | ||
Weight of the Power Module [kg] | 41 | |
Dimensions of the Power Module (WxDxH) [mm] | 445(19”)x664x397(9U) | |
Weight of the cabinet [kg] | 165 (Power Modules excluded) | |
Dimensions of the
cabinet (WxDxH) [mm] |
700x750x2060 (if provided by Riello UPS) | |
Maximum number of Power Modules for cabinet | 3 | |
Communications for each Power Module | UPS status led bar - 5 inch graphic touch screen display - 2 slots for communications interface
USB - RS232 - Contact interface with 5x opto insulated Input and 4x Output relays |
|
Ambient temperature
for the Power Module |
0 °C - +40 °C | |
Recommended temperature for battery life | +20 °C - +25 °C | |
Range of relative humidity | 5-95% non-condensing | |
Colour | RAL 9005 | |
Noise level at 1 m [dBA ±2]
SMART ACTIVE |
<40 for the single power module | |
IP rating | IP20 | |
SMART ACTIVE efficiency | up to 99% | |
Standards | European directives: LV 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility
Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111 |
|
Moving the parts | Pallet jack (UPS cabinet) - 2 operators (UPS Power Module |