Suggested applications: Servers rooms, hospitals, data centres, banking and IT
CertaUPS C750-100-B Power Control 10kVA with a unity power factor and the ability to configure the UPS as three phase or single phase, the online double conversion C750 series offers the user ultimate flexibility. It also features out of the box connectivity with the IoT monitoring via the CertaUPS monitor app.
Key Features:
• Unity Power Factor
• Pure Sine wave
• Online double conversion
• Single or three phase (3/3, 3/1 or 1/1)
• Single source or dual source input
• Colour touch screen LCD display
• Expandable runtime
• Out of the box connectivity
• High efficiency up to 95%
• Small footprint
Model | C750-100-B |
Capacity | 10kVA/10kW |
INPUT | ||
Input Voltage Range | 110VAC - 300VAC | |
Rated Voltage | 220/230/240VAC or 380/400/415 VAC | |
Main input rated current (3 phase) | 22A | |
Main input rated current (1 phase) | 65A | |
Bypass input rated current (3 phase) | 16A | |
Bypass input rated current (1 phase) | 47A |
Frequency | 40Hz/70Hz |
Frequency Range | 45Hz-55Hz (50Hz system), 54Hz-66Hz (60Hz system) @ load>60% |
Bypass input frequency | 45-55Hz(50Hz system) / 54-66Hz(60Hz system) |
Power Factor | 1 |
OUTPUT | ||
Voltage Regulation (AC Mode) |
220/230/240VAC
380/400/415VAC |
|
Maximum Power Factor | 1 | |
Transfer Time Line <-> Battery | 0ms | |
Transfer Time INV<-> Bypass | 0ms | |
Wafe form | Pure sine wave | |
Short Circuit Current on Normal Mode (3 phase output) | 30A for 10±1 cycle | |
Short Circuit Current on Normal Mode (1 phase output) | 90A for 10±1 cycle |
Overload Capacity |
105%-125% Load, 10 minutes transfer to Bypass; 125%-150% Load, 30 seconds transfer to Bypass;
>150% Load, 0.5 seconds transfer to Bypass |
|
BATTERY | ||
Voltage | 192VDC or 240VDC Selectable |
PHYSICAL | |
Dimension (WxDxH) mm | 300 x 633.2 x 805.5mm |
Net weight (Kg) | 106 |